Discharge instrument

2023/02/28

Model:ZKHY-FDY301

Type:

Suitable for battery discharge testing in power bureaus, power plants, substations, communication companies, and UPS uninterruptible power supplies

Rated discharge current: 50A × N (n=1-16)
Applicable battery capacity: 500-8000Ah
Single unit discharge current: 0.1-50A continuously adjustable
Discharge voltage: 48/110/220/392VDC
Discharge time: 1min~176h
DC current ripple coefficient < 0.1%
Constant current accuracy ≤ 0.3%
Current adjustment fineness: 0.1%
Heat dissipation method: forced air cooling
Mean time between failures: ≥ 200000 hours

Related Product: